Repair of a Weiss Technik Temperature and Humidity Test Chamber with Refrigerant Leakage in Bac Ninh

  • News
  • 94 views

Last June, the VintechME engineering team directly supported a customer in inspecting and repairing a Weiss Technik C7-270/15 temperature and humidity test chamber that was experiencing an unusually slow cooling rate. Following an on-site inspection, the root cause was identified as an insufficient amount of refrigerant in the refrigeration system. The article below presents the detailed process of analysis, diagnosis, and corrective action for this issue.

Table of Contents

Post-Repair Operational Check

The Weiss Technik temperature and humidity test chamber is one of the most widely used environmental testing systems in the automotive, electronics, semiconductor, aerospace, defense, and medical device industries. With its highly accurate temperature and humidity control capabilities, the equipment helps companies evaluate product durability, reliability, and service life in accordance with international standards.

However, after many years of operation or without regular maintenance, a Weiss Technik test chamber may develop refrigeration system problems. One of the most common issues is an insufficient amount of refrigerant. This fault reduces cooling capacity, prevents the equipment from achieving the specified temperature change rate, and directly affects test results.

Recently, the VintechME engineering team directly supported a customer in inspecting and repairing a Weiss Technik C7-270/15 temperature and humidity test chamber that was experiencing an unusually slow cooling rate. Following an on-site inspection, the root cause was identified as an insufficient amount of refrigerant in the refrigeration system. The article below presents the detailed process of analysis, diagnosis, and corrective action for this issue.

Customer-Reported Issue

The customer was operating a Weiss Technik C7-270/15 temperature and humidity test chamber with the following technical specifications:

  • Designed cooling rate: 15°C/min

  • Test program:

    • Hold at 85°C

    • Then cool down to -45°C

In theory:

  • The total temperature difference is 130°C

  • At a cooling rate of 15°C/min, the chamber should reach -45°C in approximately 8.7 minutes

However, during actual operation:

  • After 10 minutes, the chamber temperature had only decreased to approximately 20°C

  • The equipment failed to achieve the cooling rate specified by the manufacturer

  • The actual temperature curve remained significantly higher than the programmed setpoint

This issue extended the total test duration and affected temperature cycling tests, environmental durability tests, and product reliability evaluations.

VintechME Engineer’s On-Site Inspection Process

After receiving the service request, the VintechME engineering team carried out a systematic inspection of the equipment in order to accurately determine the cause of the problem.

1. Alarm History Check

The engineers first reviewed the complete alarm history of the equipment.

The inspection results showed:

  • No controller faults

  • No high-pressure or low-pressure alarms

  • No temperature sensor faults

  • The test program was running normally

These findings indicated that the control system was not the cause of the slow cooling performance.

2. Heating Performance Check

The engineers then ran a heating test program.

The results showed:

  • The heating rate met the design specification

  • The temperature increased steadily

  • No temperature fluctuation or overheating was observed

This allowed the engineers to rule out possible faults involving:

  • Heater elements

  • Heating SSR

  • PID controller

  • Operating program

The results confirmed that the heating system was operating normally.

3. Refrigeration System Check

Because the fault occurred only during cooling, the complete refrigeration system was inspected in detail.

The inspection included:

  • Compressor suction pressure

  • Discharge pressure

  • Suction line temperature

  • Discharge line temperature

  • Compressor operating current

  • Cooling fan operation

  • Condenser operation

  • Evaporator operation

After measurement and inspection, the engineers identified the following conditions:

  • Suction pressure was lower than the standard operating value

  • Cooling performance had noticeably decreased

  • The compressor continued to operate, but the cooling capacity was very poor

  • The cooling time was significantly longer than the design requirement

These are typical signs of an insufficient refrigerant charge.

Root Cause – Insufficient Refrigerant

After reviewing all on-site inspection and measurement results, VintechME determined the root cause of the problem as follows:

The refrigeration system of the Weiss Technik test chamber contained an insufficient amount of refrigerant, resulting in reduced cooling capacity and preventing the chamber from achieving the designed cooling rate.

Although the compressor was still operating, the amount of refrigerant circulating through the system was not sufficient to absorb and transfer heat from the test space to the outside environment.

This is a common issue in Weiss Technik environmental test chambers that have been operating for an extended period or have developed refrigerant leaks at pipe connections, welded joints, or service valves.

Why Does Low Refrigerant Cause a Weiss Technik Test Chamber to Cool Slowly?

The refrigeration system of a Weiss Technik test chamber operates based on a vapor-compression refrigeration cycle.

In this cycle, the refrigerant absorbs heat at the evaporator and releases heat at the condenser.

When the refrigerant charge is insufficient:

  • Refrigerant circulation flow decreases

  • The heat absorption capacity of the evaporator is reduced

  • Heat transfer efficiency decreases

  • Cooling capacity drops significantly

  • The compressor must operate continuously for a longer period

  • The chamber temperature decreases very slowly

Continued operation under these conditions may lead to:

  • Longer test cycles

  • Failure to achieve the required temperature change rate

  • Increased energy consumption

  • Reduced compressor service life

  • Potential damage to refrigeration system components

VintechME’s Repair Solution

After accurately identifying the cause, the VintechME engineering team carried out the repair process in accordance with proper technical procedures.

Refrigerant Leak Inspection

The complete refrigeration system was inspected to identify the source of refrigerant loss.

The following areas were checked:

  • Refrigerant pipe connections

  • Service valves

  • Welded joints

  • Condenser

  • Evaporator

If a leakage point is detected, it must be completely repaired before new refrigerant is charged into the system.

System Vacuuming

After confirming that the refrigeration system was fully sealed, the engineers vacuumed the system in order to:

  • Remove air

  • Remove moisture

  • Ensure a clean internal refrigeration circuit

  • Improve cooling performance after refrigerant charging

Refrigerant Charging to the Correct Specification

VintechME used the correct refrigerant type recommended by Weiss Technik and charged the system with the quantity specified by the manufacturer.

Using the correct refrigerant type and charging the correct amount are essential for achieving optimum cooling performance and protecting the compressor’s service life.

Post-Repair Operational Check

After completing the refrigerant charging process, the engineers continued to inspect:

  • Suction and discharge pressures

  • Compressor operating current

  • Cooling rate

  • Temperature stability

  • The complete test chamber operating program

The results showed that:

  • The equipment regained the cooling rate specified by the manufacturer

  • The actual temperature closely followed the programmed setpoint

  • The test cycle operated stably

  • The refrigeration system returned to normal operation

The Weiss Technik test chamber was restored to stable operating condition and once again met the customer’s testing requirements.

Recommendations from VintechME

To keep a Weiss Technik temperature and humidity test chamber operating reliably, VintechME recommends performing preventive maintenance every 6 to 12 months.

The following items should be checked:

  • Refrigeration system pressure

  • Refrigerant charge level

  • Refrigerant leakage

  • Condenser and evaporator cleanliness

  • Compressor performance

  • Cooling fan operation

  • Temperature and humidity sensor calibration

  • Test chamber temperature change rate

Regular maintenance helps detect early signs of performance degradation, prevent major failures, and extend the service life of the equipment.

VintechME – Specialist in Weiss Technik Test Chamber Repair and Maintenance

VintechME specializes in the repair, maintenance, and calibration of Weiss Technik temperature and humidity test chambers, thermal shock chambers, walk-in chambers, and many other environmental testing systems.

Our services include:

  • On-site inspection and fault diagnosis

  • Refrigeration system repair

  • Refrigerant leak detection and repair

  • System vacuuming and refrigerant charging

  • Replacement of compressors, electronic expansion valves, and refrigeration components

  • Temperature and humidity calibration

  • Preventive maintenance and equipment performance optimization

  • Nationwide technical support

With an experienced engineering team and a professional inspection process, VintechME is committed to delivering fast, effective, and cost-efficient solutions. Our services help businesses reduce equipment downtime and ensure that testing processes continue to meet the required level of accuracy.

Images from the Inspection and Repair Process

Sửa chữa chamber nhiệt ẩm Weiss Technik bị rò gas


Tháo vỏ máy để kiểm tra và sửa chữa chamber nhiệt ẩm Weiss Technik bị rò gas

Kiểm tra hệ thống điện chamber nhiệt ẩm Weiss Technik

Kiểm tra hệ thống lạnh chamber nhiệt ẩm Weiss Technik bị rò gas

Contact VintechME Vietnam

Contact VintechME if your Weiss Technik temperature and humidity test chamber experiences any of the following problems:

  • Cooling performance is slower than the design specification

  • The chamber cannot achieve the required temperature change rate

  • The compressor operates continuously but cooling performance remains poor

  • The actual temperature consistently lags behind the programmed setpoint

  • Test cycles take significantly longer than normal

The VintechME engineering team is ready to provide prompt inspection, diagnosis, and repair support.

VINTECHME VIETNAM JSC

Hotline: 0966 252 565
Email: info@vintechme.com
Website: https://vintechme.com

Sign up for a news